INSTALLATION INSTRUCTIONS
C-WR-A-WW4-SCCT LED Series
NOTE: The emergency driver and AC driver must be fed
from the same branch circuit.
Make the following Electrical Connections:
STEP 1: (Connecting the Occupancy Sensor)
a. Connect the black fixture lead labeled switched
hot to the red lead from the occupancy sensor.
b. Connect the violet fixture lead to the violet lead
from the occupancy sensor.
c. Connect the grey or pink fixture lead to the grey or
pink lead from the occupancy sensor.
STEP 2:
a. Connect the black fixture lead labeled unswitched
hot to the unswitched voltage supply lead.
b. Connect the black lead from the occupancy sensor
to the switched voltage supply lea..
c. Connect the white fixture lead and the white lead
from the occupancy sensor to the neutral supply
lead (Hot 2 for 208/240V wiring).
d. Connect the bare or green ground fixture lead to
the supply ground lead.
Tuck all wires carefully into wiring chamber ensuring that
no wires are pinched.
STEP 3:
Turn on the unswitched supply to the fixture. Keep the
switched voltage supply to fixture off.
STEP 4:
Plug the female connector on the ends of the leads
from the battery into the male connector on the emer-
gency driver. Plug should click into place. See Figure
11.
WARNING: Do NOT mate the connector on the battery
leads to the emergency driver until AC power has been
supplied to the emergency driver.
ELECTRICAL CONNECTIONS-
Emergency Driver and Occupancy Sensor
*** NOTE: Do NOT mate the connector on the battery leads to the
emergency driver until AC power has been supplied to the
unswitched hot lead to the fixture.
http://lighting.cree.com/warranty
Document:
LPN00867X0001A1_A
Created By:
TMT
LINE SWITCHED
LINE- UNSWITCHED
NEUTRAL OR HOT 2
GROUND
|
866.924.3645
Date:
12-08-2021
LUMINAIRE
OCCUPANCY SENSOR
LINE - BLACK
RED
WHITE
VIOLET
GREY OR PINK
LINE - BLACK
UNSWITCHED
LINE - BLACK
SWITCHED
NEUTRAL - WHITE
VIOLET
GREY OR PINK
BARE OR
GREEN
*** MALE CONNECTOR
EM DRIVER
*** FEMALE CONNECTOR
BATTERY PLUG