ATS time setting guide
ATS Box - Version 10013677 / 10013678
After 5 seconds of recovering grid power from the outage, the PCS stops the backup mode. At
the same time, supplies power to the critical load and the PCS. The PCS will be restarted in normal
mode.
Using the EnerVu application, you can set the interval of restarting the system after power recovery.
Follow the steps as described below.
1. In the EnerVu application, select [Installer settings] > [PCS] > [Grid] > [Reconn. Condition
(Tripping)] > [Observation Time].
2. Enter an interval value in the [Observation Time] option. The default value is 60 (sec) and the
minimum value you can set is 30 (sec).
ATS Box - Version 10013679 (Bender VMD460)
After 5 seconds of recovering grid power from the outage, the PCS stops the backup mode. The
power will be supplied to the critical load and the PCS after the time set by the ATS box.
And then, the PCS automatically restarts in normal mode.
Using the EnerVu application, you can set the interval of restarting the system after power recovery.
Follow the steps as described below.
1. In the EnerVu application, select [Installer settings] > [PCS] > [Grid] > [Reconn. Condition
(Tripping)] > [Observation Time].
2. Enter an interval value in the [Observation Time] option. The default value is 60 (sec) and the
minimum value you can set is 30 (sec).
If the time setting in ATS box is 30 seconds and the PCS settings in [Observation Time] option is 60
seconds, the PCS restarts in 90 seconds after power recovery.
Settings