The qualified personnel can also install a single electromechanical
component including an RCD and MCB.
MCB
The electrical power for
fitted to the switchboard to protect the electrical circuit.
The minimum features of the MCB must be: voltage 250V, nominal current
32A (in the hypothesis of absorption of the maximum power of 7.4 kW).
If local regulations do not allow the maximum power to be absorbed, the
qualified personnel must choose a breaker with nominal current based on
the maximum power allowed when installed, as intervention curve, a type C
curve for domestic or similar use is suggested.
In the event of a short circuit, the value of I2t to the vehicle connector
(Case C) of the recharging device in Power Upgrade mode must not
exceed 80 000 A2s.
When the MCB is sized, the presumed short-circuit current must be
considered. The value of 5kA could be considered as an indicative value
but a precise assessment must be made before installation. The maximum
breaking capacity of the MCB must be higher than the presumed short-circuit
current assessed.
The MCB must be in line with the section of the cables.
Remember that there may be local regulations to apply that may vary
according to the region/country of installation.
installed respecting local regulations.
2 fuses of 1A and 250V are integrated into the supply channel of the logic
in easyWallbox.
When the breaker is sized, the maximum environmental temperatures
reached inside the electrical cabinet should be considered.
easyWallbox
must be installed on a special MCB
easyWallbox
must be