5.1. MOVING AND STORAGE
Without hoist ring
With hoist ring
If the generator is to be stored before to use, adequate facilities must be provided, free of
dust and moisture, and the unit must be protected from chemical agents that could
damage it or could damage any of its components.
If storage is expected for more than five months, it is advisable to remove engine oil and
filters until the equipment is used. Battery must be turn off.
0 6 .
STARTING UP
Before starting up a generator, check that:
•
batteries are correctly connected;
•
earthing has been properly established;
•
all electrical connections have been made;
•
the installation of the group complies with the conditions established by the manufacturer
and the legislation in force;
•
oil levels are correct;
•
antifreeze levels are correct;
•
fill the fuel tank with at least 20%, but not more than 90%;
•
start the generator in the controller for 1 minute at no load;
•
after 3 months without functioning: it is recommended to add an antibacterial product
to the fuel;
•
after 6 months of non-operation: must proceed as defined by the engine manufacturer,
regarding long-term storage.