Specifications
Model
Overload capacity in battery
mode
Current limitation
Autonomy time at full load
Battery recharge time
Transfer time
Outlets
Maximum input current
Storage and Service
Storage
To avoid battery drain, all connected equipment should be turned off and disconnected from
the UPS. Press the power button and disconnect the unit from AC power. Your UPS will be
completely turned off (deactivated), and will be ready for storage. If you plan on storing your
UPS for an extended period, fully recharge the UPS batteries every three months. Plug the
UPS into a live AC outlet, turn it on by pressing the power button and allow the batteries to
recharge for 4 to 6 hours. If you leave your UPS batteries discharged for a long period of time,
they will suffer a permanent loss of capacity.
OMNI700LCDT
110% @ 5 minutes
Both 10A
3 minutes @ 350W
8 hours
6 milliseconds typical
(6 milliseconds max)
4x 5-15R outlets with battery
backup, regulation and surge;
2x 5-15R outlets only for
surges
10A
10
OMNISMART500TU
110% @ 5 minutes
Input 7A
Output 6A
3 minutes @ 360W
8 hours
6 milliseconds typical
(6 milliseconds max)
4x 5-15R outlets with battery
backup, regulation and surge;
2x 5-15R outlets only for
surges
6A