Battery Replacement
Under normal conditions, the original battery in your UPS will last several years. Battery
replacement should only be performed by qualified personnel. Refer to "Battery Warnings" in
the Important Safety Instructions section for more information.
The OMNI700LCDT and OMNISMART500TU require one 12V DC, 9AH replacement battery.
For further information about replacement compatibility and ordering, visit
www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and
quantity: 12V DC sealed lead-acid, 6-cell and in compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove
conductive jewelry such as chains, wristwatches and rings. High energy
passing through conductive materials may cause severe burns.
Specifications
Model
Nominal input voltage(s) and
range
Nominal input frequency and
tolerance
Nominal output voltage
Nominal output frequency
Output voltage regulation in
line-mode
Output voltage regulation in
battery mode
Nominal output power in W
/ VA
Output voltage waveform
Maximum output current @
P .F.
Efficiency with nominal load
Maximum operating altitude
at 100% of nominal power
Online overload capability
OMNI700LCDT
120V~, 89-145V~
50/60 Hz (+/- 5 Hz)
120V~ sinusoidal in line
mode and 120V~ PWM in
battery mode
50/60 Hz (+/-0.5 Hz)
120 V~ (+9% / - 12%)
120V~ (+/-10%)
350W / 700VA
Sinusoidal in line mode and
quasi-sine (PWM) in battery
mode
5.8A @ 120V~
P .F. = 0.5
95%
6561 ft. (2000 m) above
sea level
110% @ 5 minutes
9
OMNISMART500TU
120V~, 89-145V~
50/60 Hz (+/- 5 Hz)
120V~ sinusoidal in line
mode and 120V~ PWM in
battery mode
50/60 Hz (+/-0.5 Hz)
120 V~ (+9% / - 12%)
120V~ (+/-5%)
360W / 500VA
Sinusoidal in line mode and
quasi-sine (PWM) in battery
mode
4.2A @ 120V~
P .F. = 0.72
95%
6561 ft. (2000 m) above
sea level
110% @ 5 minutes