Descargar Imprimir esta página

Victron energy MultiPlus 12 500 20 Manual página 17

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 87
5.4.2. DIP switch 2 to 6
These DIP switches can be used to set:
- Battery charge voltage and Absorption time
- Inverter frequency
- Search mode
Ds2-ds3: Setting the charge algorithm
Absorption
ds2-ds3
voltage
ds2=off
14.4
ds3=off
28.8
(default)
57.6
ds2=off
14.1
ds3=on
28.2
56.4
ds2=on
14.7
ds3=off
29.4
58.8
ds2=on
15.0
ds3=on
30.0
60.0
Ds4: Inverter frequency
Ds5: Search Mode
Store the settings by moving DIP switch 6 to 'on' and back to 'off'.
18
Float
Storage
voltage
Voltage
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
13.8
13.2
27.6
26.4
55.2
52.8
off = 50Hz
off = off
Absorption
Time
Suitable for
(hours)
Gel Victron Deep
Discharge
8
Gel Exide A200
AGM Victron Deep
Discharge
Gel Victron Long
Life (OPzV)
Gel Exide A600
8
(OPzV)
Gel MK battery
Li-ion (LiFePO4)
AGM Victron Deep
Discharge
Tubular plate or
5
OPzS batteries in
semi-float mode
AGM spiral cell
Tubular plate or
6
OPzS batteries in
cyclic mode
on = 60Hz
on = on

Publicidad

loading