Intended use
- Chain drive for electric opening and closing of heavy
windows and flaps in the facade and roof area
- Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as
daily natural ventilation
- Only for inside mounting
Safety notes
Operating voltage 24 V DC!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed r ed safety slip!
Functional description
A synchron-group (CDP-TW -BSY+) can be count up
to 2 drives, which communicate by a bus.
Each drive has it's own adress.
This adress is configurable with SCS.
The last drive of a synchron-group is the master,
which controls the other drive, the slave. Different
forces between the drives of a group will balanced
with intelligent force- and position control. In case of
malfunction respective cutoff of a drive or a position
difference ≥ 30 mm, all drives will shut down from the
master-drive.
Extent of supply
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
6/24
CDP-TW-BSY+
Performance features
- Micro processor controlled synchro electronics
BSY + for a precise synchronous run of up to
2 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Locking relief after closing
- Especially quiet motor running in ventilation mode
- Symmetrical chain outlet
- Connection via pin-and-socket connector
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Pressure load diagram
Observe maximum pressure load of the chain!
Maximum pressure load per chain is not
automatically identical with maximum pressure force
of the drive!
3000
total
2500
2000
1500
per chain
1000
500
0
Trouble shooting
Visual inspection:
Only one master and one slave drive allowed.
The adress is sticked on the drive.
Example: In a group, composed of 3 drives,
there is a master 3, a slave 2 and a slave 1drive.
Attention: only applies by factory set.
As soon as the drives were reprogrammed with
SCS the addressing might vary from
factory set addressing.
Wiring:
Is the group wired correctly?
Therefore look connection diagrams.
Null balance:
It should be null balanced. (Page 8)
Software SCS or the special magnet
MAG 502 is required.
Call D+H Service:
Drives must be configured.
Software SCS is required.
English
Stroke (mm)
99.825.21 1.7/10/21