EN
Function
General safety functions
Operating function
- If heat is requested by the boiler
thermostat, the automatic oil
combustion control unit starts the
program sequence.
- The motor starts, the igniter is switched
on and the preventilation period of 15
seconds commences.
- During the preventilation period, the
furnace is monitored for flame signals.
- At the end of the preventilation period,
the fuel-oil solenoid valve opens and the
burner starts.
- The igniter remains switched off while
the burner is in operation.
Controlled shutdown
- Boiler thermostat interrupts heat
request.
- The fuel-oil solenoid valve closes and
the flame is extinguished.
- Burner motor switches off.
- Burner enters standby.
105
8
www.ecoflamburners.com
Safety function
A safety shutdown occurs:
- if a flame signal is present during
preventilation (parasitic flame
monitoring).
- if no flame is produced within 5 seconds
(safety time) of start-up (fuel
authorisation).
- if no flame is produced after an
unsuccessful restart attempt in the
event of flame failure during operation.
A safety shutdown is indicated by the
malfunction lamp lighting up and it is then
only possible to reenable the burner by
pressing the reset button after the cause
of the malfunction has been rectified.
For further information, see the
automatic combustion control unit
description.
101
103
M
M1
106
Y1
M1
T1
102
Y1
101
102
103
104
104
105
106
118
T1
118
Burner motor
Ignition Transformer
Solenoid valve
Blower / Fan
Oil pump
Air damper
Oil pressure regulator
Hoses
Filter
Nozzle
420011054800