Setup by pushing the button: In order to start the editing mode for parametrizing you must select the respective
item in the parametrizing loop and then push the button once again for 2-3 seconds. As an aid, after 2 seconds the
„editing pen" will be displayed bottom left in the LCD (see below picture). As soon as it appears you have to let go
of the button. Then the current display will start blinking.
By pressing the push-button briefly you can switch to the next option. By pressing the push-button longer the
currently displayed option will be set. If no option is chosen there will be no change and as soon as the LCD goes
out the edit mode will end automatically.
b) The following characteristic of those mechanical meter types designed to be used with glycol can be set on
location at any time using the „Device Monitor" software:
-
type and concentration of glycol in the medium (propylene glycol; ethylene glycol; 20 %; 30 %; 40 %; 50%).
8.2 Detection of flow
As long as the meter detects some flow the following pictogram will be displayed bottom right in the LCD.
flow detected
9 Application Conditions
SensoStar
Maximum flow qs/qp
Mechanical class
Electromagnetic class
Environmental class
Protection class flow sensor
Nominal pressure PN
Mounting position
SensoStar E
Flow sensor of
Temperature range medium heat
Temperature range medium cooling
SensoStar U
Flow sensor of
Temperature range medium heat
Temperature range medium cooling
Temperature range medium
heat/cooling
Calculator
Ambient temperature in the field
Transport temperature
Storage temperature
Protection class
10 Interfaces and Options
10.1 Optical (infrared) interface
For communication with the optical interface an optocoupler and the "Device Monitor" software are necessary.
The optocoupler and "Device Monitor" are available as accessory equipment.
The optical infrared interface will be activated by automatically sending a header (according to EN 13757-3). Baud
rate: 2400 baud.
Then you can communicate with the meter for 4 seconds. After every valid communication the meter is open for
another 4 seconds. Afterwards the display is deactivated.
Page 10 of 50
Article no.: 1080621033
2:1
M2
E2
C
IP65
bar
16
any, if there is no indication on type label
SensoStar
and
multi-jet heat meters
°C
15 – 90
°C
5 – 50 (qp 1,5 and qp 2,5)
°C
15 – 90
15 – 130 high temperature (150; for maximal 2000 h) (optional)
°C
5 – 50 (from qp 1,5 to qp 10)
°C
15 – 90 heat
15 – 120 high temperature (optional)
5 – 50 cooling
°C
5 – 55 at 95 % relative humidity
°C
-25 – 70 (for maximal 168 h)
°C
-25 – 55
IP65
2022-02-04