Descargar Imprimir esta página

Eaton EASY256-HCI Instrucciones De Montaje página 2

Publicidad

EASY256-HCI
Standard connection
for increasing the input current with EASY256-HCI
L
N
S..
> 1 A
L
N
N
115/230 V h
Switch-on/switch-off delay
S..
I..
a
b
c d
Attention! Inrush peaks!
Do not use reed contacts with EASY256-HCI.
These contacts may burn out due to the high inrush current.
HAZARDOUS LOCATION – CSA (Canadian Standards Association) Certification
This equipment is suitable for use in CLASS I, DIVISION 2, GROUPS A, B, C AND D
WARNING: "EXPLOSION HAZARD – DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN
TO BE NON-HAZARDOUS"
EMPLACEMENTS DANGEREUX – Certification CSA (Canadian Standards Association)
Cet équipement est acceptable pour utilisation dans les EMPLACEMENTS DANGEREUX DE CLASSE I, DIVI-
SION 2, GROUPES A, B, C ET D
AVERTISSEMENT : « RISQUE D'EXPLOSION. NE PAS DÉBRANCHER TANT QUE LE CIRCUIT EST SOUS TEN-
SION, A MOINS QU'IL NE S'AGISSE D'UN EMPLACEMENT NON DANGEREUX »
2/2
EU: Eaton Industries GmbH, Hein-Moeller-Straße 7-11,
53115 Bonn, Germany
UK: Eaton Electric Ltd., P.O. Box 554, Abbey Park,
Southampton Road, Titchfield, PO14 4QA, United Kingdom
UL/CSA: Maximum operating ambient temperature 55°C
S..
I1
I2
I3
I4
I5
.....
Input 115/230 V h
a Normal ON delay
b Switch-on state detected
c Normal OFF delay basic unit
d Additional OFF delay EASY256-HCI
50 Hz: ~ +40 ms, 60 Hz: ~ +37 ms
EASY256-HCI
N
N
1
2
3
4
5
6
Eaton.com/contacts
Eaton.com/aftersales
Eaton.com/documentation
USA: Eaton.com/eatoncare
© 2001 Eaton Industries GmbH
11/22 IL05013009Z
Eaton.com/recycling

Publicidad

loading