DC Inverter U-match Series Floor Ceiling Type Unit
Tighten the clamp until the screw
head is less than 4 mm from the hose
①.
- Metal clamp
②.
- Drain hose
③.
- Grey tape
4) When drain hose requires extension, obtain an extension hose commercially
available.
5) After connecting the local drain hose, tape the slits of the heat insulation tube.
6) Connect the drain hose to the local drain pipe. Position the inter connecting
wire in the same direction as the piping.
3.2.6.2 Connecting the Drain Hose
(1) Connect the extension auxiliary pipe to the local piping.
(2) Prepare the local piping at the connection point for the drain pipe, as shown in
the installation drawings.
Notice: Be sure to place the drain hose as shown in the diagram below, in a
downward sloping direction.
3.2.6.3 Outdoor Side Drainage Pipe
(1) If the outdoor unit is underneath the indoor unit, arrange the pipeline according
to the following diagram.
1) Drain hose should be placed on the ground and its end should not be
immersed into water. The whole pipeline should be supported and fixed onto
the wall.
Insulate the pipe clamp and the drain
hose using heat insulation sponge.
①.
- Metal clamp
②.
- Insulation sponge
30