8-3. Operating the High-spec Wired Remote
Controller (CZ-RTC5A)
[
]
START
How to set the external static pressure
1. Keep pressing the
buttons simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the
LCD display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
2. Press the
or
menu. If you wish to see the next screen instantly,
press the
or
Select "8. Detailed settings" on the LCD display
and press the
button.
Maintenance func
5. Sensor info.
6. Servicing check
7. Simple settings
8. Detailed settings
Sel.
Page [
The "Detailed settings" screen appears on the LCD
display.
Select the "Unit no." by pressing the
button for changes.
Detailed settings
Unit no.
Code no.
3-1
Sel.
Next
3. Select the "Code no." by pressing the
button.
Change the "Code no." to "5D" by pressing the
or
button (or keeping it pressed).
20:30 (THU)
,
and
20:30 (THU)
] Confirm
button to see each
button.
20:30 (THU)
] Confirm
or
20:30 (THU)
Set data
10
0006
or
Detailed settings
Unit no.
3
1 -
Sel.
4. Select the "Set data" by pressing the
button.
Select one of the "Set data" among "0006", "0003"
or "0001" according to the desired external static
pressure setting by pressing the
button. (See Table 8-3 and Fig. 8-2.)
Then press the
Table 8-3 Setting the external static pressure
Indoor unit
200
External static pressure of the rated
air flow volume
270 Pa
140 Pa
60 Pa
5. Select the "Unit no." by pressing the
button and press the
The "Exit detailed settings and restart?" (Detailed
setting-end) screen appears on the LCD display.
Select "YES" and press the
Detailed settings
Exit detailed settings
Unit no.
1-1
Sel.
19
20:30 (THU)
Code no.
Set data
5D
0 0
1 0
Next
or
button.
Item code
250
5D
0006
270 Pa
0003
140 Pa
72 Pa
0001
button.
button.
20:30 (THU)
Code no.
Set data
and restart?
10
0001
YES
NO
Next
or
or

Publicidad

loading