Editing Default Values - Waeco AirConServiceCenter ASC 5300 G Instrucciones De Uso

Ocultar thumbs Ver también para AirConServiceCenter ASC 5300 G:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Initial start-up
7.7

Editing default values

The AirConServiceCenter has preset values for the most important ser-
vice tasks. The default values appear automatically when you select the
respective menu.
You can alter the following default values if necessary:
Parameter
Pressure increase test time min.
Vacuum time min.
Leak test min.
PAG oil ml. (additional quantity)
UV tracer ml.
Filling Qt. g.
Print recovery value?
1. In the basic menu, use the cursor keys  or  to select "Other
selections":
2. Press ENTER to confirm.
3. Use the cursor key  to select "Service".
4. Press ENTER to confirm.
5. Enter the password "7388".
6. Use the keypad and the cursor keys to enter the information.
7. Press ENTER to confirm.
8. Press STOP to access the standby menu.
84
Short selection
Free selection
Other selections
ENTER-OK
ASC 5300 G
Default value
5
20
4
0
0
500
Yes
EN

Publicidad

Tabla de contenido
loading

Tabla de contenido