Descargar Imprimir esta página

GE GEH Guía De Instalación Rápida página 20

Publicidad

Cable Specifications | Especificaciones de los cables | Caractéristiques des câbles
No.
Terminal/Port
1
PV input terminal
2
Grouding busbar
3
Battery input terminal
4
Generator
communication
terminal
5
Load control
communication
terminal
6
USB port
7
Battery
communication
terminal
8
Emergency stop I/O
terminal
9
Dry contact
communication
terminal
10
Meter communication
terminal
11
ABD/MPD
communication
terminal
12
LAN communication
terminal
13
SIM card slot
14
Parallel connection
port
15
EV charger port
16
AC cable terminal
17
EMS communication
terminal
Silkscreen
Recommended Cable Specifications
PV INPUT
90℃ (194°F) copper cables, 12-10AWG.
-
90℃ (194°F) copper cables, 10-6AWG.
BAT INPUT
90℃ (194°F) copper cables, 6AWG.
GEN
outdoors communication cables that meet UL2919,
CM/CMG (NEC type), or CMH (CSA type) requirements,
6AWG.
LOAD CNTL
outdoors communication cables that meet UL2919,
CM/CMG (NEC type), or CMH (CSA type) requirements,
24-16AWG.
U DISK
-
EMS/CAN
outdoors communication cables that meet UL2919,
CM/CMG (NEC type), or CMH (CSA type) requirements,
24-16AWG.
E-STOP
outdoors communication cables that meet UL2919,
CM/CMG (NEC type), or CMH (CSA type) requirements,
24-16AWG.
DRY_IN
outdoors communication cables that meet UL2919,
CM/CMG (NEC type), or CMH (CSA type) requirements,
cross-sectional area range 24-16AWG.
Meter
outdoors communication cables that meet UL2919,
CM/CMG (NEC type), or CMH (CSA type) requirements,
24-16AWG.
ABD/MPD
CAT 5E outdoor shielded network cable and shielded
RJ45 connector
LAN
CAT 5E outdoor shielded network cable and shielded
RJ45 connector
4G SIM
size: 25mm x 15mm (0.98 in x 0.59 in)
CARD
capacity ≥64KB
PAR-1,
-
PAR-2
EV OUTPUT
-
AC INPUT
90℃ (194°F) copper cables, 6AWG.
EMS
-
18

Publicidad

loading

Este manual también es adecuado para: