01 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
You shall follow all the safety precautions mentioned in this guide when working on or with the
equipment.
General Disclaimer
• The information in this quick installation guide is subject to change due to product updates
or other reasons. This guide cannot replace the product labels or the safety precautions in
the user manual unless otherwise specified. All descriptions here are for guidance only.
• Before installations, read through the quick installation guide. For additional information,
please see the user manual.
• All operations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
• Check the deliverables for correct model, complete contents, and intact appearance. Contact
the manufacturer if any damage is found or any component is missing.
• Use insulating tools and wear personal protective equipment when operating the equipment
to ensure personal safety. Wear anti-static gloves, clothes, and wrist strip when touching
electronic components to protect the inverter from damage. The manufacturer shall not be
liable for any damage caused by static electricity.
• Strictly follow the installation, operation, and configuration instructions in this guide and
user manual. The manufacturer shall not be liable for equipment damage or personal injury
if you do not follow the instructions. For more warranty details, please visit
gesolarinverter.com/warranty.html.
Safety Disclaimer
WARNING
PV panel safety:
1. Ensure the component frames and the bracket system are securely grounded.
2. Connect the DC cables using the delivered PV connectors. The manufacturer shall not be
liable for equipment damage if other connectors are used.
3. Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring
may cause poor contacts or high impedances, and damage the inverter.
4. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the
voltage should be under the max DC input voltage. The manufacturer shall not be liable for
the damage caused by reverse connection and extremely high voltage.
5. To avoid damage the inverter, do not connect one PV string to multi inverters.
Product Enclosure:
1. The voltage and frequency at the connecting point should meet the on-grid requirements.
2. Additional protective devices like circuit breakers or fuses are recommended on the AC side.
Specification of the protective device should be at least 1.25 times the rated AC output rated
current.
3. Make sure that all the groundings are tightly connected. When there are multiple inverters,
make sure that all the grounding points on the enclosures are equipotential bonding.
4. You are recommended to use copper cables as AC output cables.