Tripp-Lite SRCOOL3KTP Instrucciones De Instalación página 3

Sistema de retorno de ventilación de emergencia para unidades de aire acondicionado
Ocultar thumbs Ver también para SRCOOL3KTP:

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation
6
Lower the lid toward its closed position.
Note: The lid may not fully close until power is applied to the
electromagnet. This is normal.
7
Attach the power supply terminals to the connector on the air conditioning unit labeled VENT.
A
Network card RJ45 Port
B
Modbus TCP Port
C
Terminals for Display Data, Display Power and SRCOOLTMVENT Power
D
Power Cable Port*
* Power Cable Not Included
8
Connect the vent power supply to a utility source to provide power to the SRCOOLTMVENT.
The vent will open if there is a power loss. Therefore, if the air conditioner is supported by a UPS, the SRCOOLTMVENT
should also be connected to a UPS.
Note: If the air conditioner and vent power supply is not supported by a UPS, the air conditioner will restart when power is restored and
the vent will be open. Manual intervention will be required to lower the vent door to the closed position.
C A B D
VENT
_
+ PE _
3
6
Display
A
+
B A
B