Symptom
Fault code is shown as 14 and the
icon
is lighting on LCD
display and alarm is continuously
sounding.
Fault code is shown as 1, 2, 3, 4,
11, 12, 13 and 41 on LCD display
and alarm is continuously
sounding.
Battery backup time is shorter
than nominal value
Possible cause
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still supplied,
but directly from AC power
via bypass.
2. The load is no longer
supplied by power.
Batteries are not fully
charged
Batteries defect
16
Remedy
Check output wiring and if
connected devices are in
short circuit status.
Contact your dealer
Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
consult your dealer.
Contact your dealer to
replace the battery.