Table 6: C23 parameter - Function of output 8.
VALUE
0
No function.
1
Fan logic; relay closed when the proportional fan is on.
Reversed fan logic; relay closed when the proportional fan
2
is off.
3
Valve logic; relay closed when the valve is opened.
4
Reversed valve logic; relay closed when the valve is closed.
5
ON/OFF logic; relay closed when the thermostat is turned on.
Reversed ON/OFF logic; relay closed when the thermostat is
6
turned off.
Economy logic; relay closed when the thermostat is in
7
economy mode or is turned off.
Reversed economy logic; relay closed when the thermostat is
8
turned on and it is not in economy mode.
Heating/cooling logic; relay closed when the thermostat is in
9
heating mode.
Reversed heating/cooling logic; relay closed when the
10
thermostat is in cooling mode.
DESCRIPTION
VALUE
11
Input 3 repeat; relay closed when the input 3 is closed.
Input 3 reversed repeat; relay closed when the input 3 is
12
opened.
13
Input 4 repeat; relay closed when the input 4 is closed.
Input 4 reversed repeat; relay closed when the input 4 is
14
opened.
15
Input 16 repeat; relay closed when the input 16 is closed.
Input 16 reversed repeat; relay closed when the input 16 is
16
opened.