Descargar Imprimir esta página

Victron energy BLUE POWER MultiPlus 12 5000 200-50 Manual página 30

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8. Technical specifications
MultiPlus
PowerControl / PowerAssist
AC input
Maximum feed through current (A)
Minimum AC supply current
capacity for PowerAssist (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25 °C (VA)
Cont. output power at 25 °C (W)
Cont. output power at 40 °C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
CHARGER
AC Input
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary output
Multi purpose relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connections
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60Hz; 120V 60Hz on request
Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 ° C ambient
5) Programmable relay which can be set for general
DC undervoltage or genset start signal function
AC rating: 230V/4A
DC rating: 4A up to 35VDC, 1A up to 60VDC
26
12/5000/200-50 230V
Input voltage range: 187-265 VAC
9,5 – 17
Output voltage: 230 VAC ± 2%
5000
(3)
4500
4000
10000
94
25
Input voltage range: 187-265 VAC
14,4
13,8
13,2
200
(4)
4
Max. 25A Switches off when no external AC source available
Material & Colour: aluminium (blue RAL 5012)
24/5000/120-50 230V
Yes
Input frequency: 45 – 65 Hz
50
6,3
19 – 33
5000
4500
4000
10000
94
25
Input frequency: 45 – 55 Hz
Power factor: 1
28,8
27,6
26,4
120
4
Yes
Yes
a - g
Operating temp.: -20 to +50°C (fan assisted cooling)
Humidity (non condensing) : max 95%
M8 bolts (2 plus and 2 minus connections)
Screw terminals 13 mm² (6 AWG)
30
444 x 328 x 240
EN 60335-1, EN 60335-2-29
EN55014-1, EN 55014-2, EN 61000-3-3
48/5000/70-50 230V
38 – 66
Frequency
50 Hz ± 0,1%
:
10000
Protection category: IP 21
5000
4500
4000
95
25
57,6
55,2
52,8
70

Publicidad