3.5.2. Water quality table
CONCENTRATION
WATER CONTENT
PER mg/l
Suspended solids
Variable
<500 µs/cm
Conductivity
>500 µs/cm
NH
2-20
3
< 300
Chlorides
>300
< 10
Iron
>10
Carbonic acids
20-50
PH
6-9
Sulphates
70-300
Langelier
-0.5 - +0.5
3.5.3. Drainage
Drainage is supplied via male R3/4" connection.
The diameter of the drainage line must be equal to or greater than the connection
diameter of the unit depending on the length and configuration of the building.
The drainage line must have a minimum slope of 2% to ensure good evacuation of
condensation.
A siphon with the correct dimensions should be made (see drawing).
If the drainage line is at a temperature below 0 degrees, it is necessary to use thermal
insulation or electrical heating cable to prevent the pipe from freezing and becoming
damaged.
UPPER VALUE
It may erode the material
No signs of damage
-
Not recommended
-
Corrosion capacity
No signs of damage
-
Corrosion capacity
Corrosion capacity
No signs of damage
Water with a tendency to create
incrustations
Recommended
SIPHON
measurements
LOWER VALUE
No signs of damage
-
Not recommended
No signs of damage
No signs of damage
-
-
Corrosion capacity
Not recommended
No signs of damage
Corrosion capacity
Water with corrosive tendency