Εnglish
A5E41370612-AC
the "SIMATIC Distributed I/O ET 200iSP" manual.
Danger
Zone 1/ 2 and safe area: In Zone 1/2 and in the safe
area, wires for the supply voltage of the Power Supply PS
DC24V at the terminal module TM-PS-A UC/TM-PS-B UC
can only be disconnected when the supply voltage has
been switched off.
Assembly
• Check the power supply for any damage! Only connect a
power supply to the TM-PS terminal module if you are
certain that the power supply is undamaged.
• In Zone 1 and Zone 2, the power supply submodules may
be inserted and removed during operation. The enclosure
(Ex e / IP 54) in which the ET 200iSP is found may only be
opened briefly for this purpose (see the "SIMATIC
Distributed I/O ET 200iSP" manual).
Commissioning
• The relevant national regulations must be observed when
commissioning the system.
• When checking the functionality of the equipment, observe
the EN 60 079-17 guidelines. This standard includes the
regulations found in the international standard
IEC 60 079-17.
For use in the USA or Canada
The control drawing for the ET 200iSP system is provided
with the Power Supply module. Alternatively, you may find the
latest edition at
http://www.siemens.com/automation/service&support
with the reference A5E00455287.