10
EN
03
Installation instructions
The work must be carried out by qualified personnel.
03.01
Packaging and scope of supply
Remove the packaging carefully, taking care not to
damage the unit.
Read these installation instructions thoroughly and
completely before you start working with the product.
Keep the installation instructions for the entire service
life of the machine and pass them on to subsequent
users.
Keep the packaging material out of the reach of
children and animals as this can lead to dangerous
situations.
Dispose of the packaging products (wood, plastic,
cardboard or polystyrene/Styrofoam) at specialised
collection points or recycling centres in accordance
with local regulations.
All components of the unit are assembled and tested
at the factory. On receipt of the machine, it must be
carefully inspected immediately for transport damage
and missing parts.
03.02
Installing the unit
The dehumidifier is to be installed on the ceiling. To do
this, the unit must be fastened using the four perforated
side lugs. Approved dowels and fasteners suitable for the
application and load case must be used for this fastening.
Installation situation
▪ The unit must be installed in a clean and dry place
protected from splashing water and drops of water.
▪ This unit is intended for indoor use in buildings.
▪ For this unit, a slope to the condensation drain of at
least 5 mm (approx. 1%) must be maintained
between the ends of the machine.
Observe correct fastening as well as sufficient
dimensioning of the dowels and fasteners on the
ceiling and on the unit.
The following should be taken into consideration:
▪ The weight of the dehumidifier
▪ The material and condition of the ceiling
▪ Possible vibrations of the dehumidifier
The ceiling must be suitable to support the weight of
the unit of 44.8 kg when filled.
▪ Be aware of the weight and sharp corners and
edges of the unit and wear suitable protective
clothing.
▪ Due to the weight, use of a construction site lift is
recommended. In addition, the installation should
be carried out by at least two people.
Check that the connections of the dowels and
fasteners on the ceiling and on the unit cannot
accidentally come loose.
The use of sound-decoupled connections is
recommended.