Air duct connection
Width
Height
When connecting to air ducts, flexible vibration
dampers must be interposed to prevent the
transmission of vibrations generated by the machine.
It is advisable to install sound absorbers on the
ventilation pipes, especially if the unit is installed in
a room in which people sleep.
Use suitable screws to mount the air duct. Seal the
connection points sufficiently with suitable materials
so that no uncontrolled air leakage can occur.
The unit front with the exhaust air opening is attached
to the unit body with screws and can be dismantled to
use the REHAU attachment for connecting ventilation
pipes.
The air volume flow is 260 m³/h at a counterpressure
through the air duct of 25 Pa at fan speed Min (3).
It should be noted that at this fan speed, the
counterpressure of the air duct does not exceed the
maximum level of 35 Pa, which corresponds to an air
volume flow of 220 m³/h. If a higher pressure loss of
the air duct cannot be avoided, the fan speed can be
changed to Med (2) or Max (1) by reconnecting the
cable on the autotransformer located in the electronics
box (see chapter 02.04).
Note that fan speeds 4, 5 and 6 must not be used.
This could damage the unit.
Dimensions
447 mm
108 mm
Unit front with exhaust air opening for the air duct
1
connection
03.04
Water-side connections
Pipe dimension
Cooling circuit
d
≥ 16 mm
Supply/Return
in
Condensation
d
≥ 16 mm
in
Water circuit
Provision of a water filter at the inlet of the
dehumidifier is recommended in order to protect the
water circuits of the unit.
Use REHAU pipe RAUTHERM-S or RAUTITAN for the
hydraulic connections to the dehumidifier (feed and
return) and observe the applicable local regulations.
Use suitable connection technology and suitable
sealing material so that no water can escape in an
uncontrolled fashion at the unit connection.
Carefully vent the water circuit using the relevant valve
on the unit as shown in the illustration. To avoid the
formation of condensation on metallic connections,
these must be insulated.
Connection
3/8" M
16 mm