Comunication cable shall be Field Supplied.
It should be used twist pair
2
cable 2 x 0,75 mm
(the
max. total length is 500 m).
It can be also used standard
shielded cable 2 x 0,75 mm
connecting the shield to
Earth at the electrical box
side (the max. total length is
500 m).
Optional Accessory Cable:
2
The cables (2x0.75 mm
twist wire) of different length are prepared as an option, which are fitted
with connectors.
Remote Control Cable (Option)
Cable Ref.
7E790211
7E790212
7E790213
7E790214
CAUTION:
- Use the twist (shield) pair cable (2 x 0.75mm²) as transmitting wire cable for prevention of the
malfunction (The total cable length is max. 500m).
When the total cable length is within 30m, other type cable (more than 0.3mm²) can be used.
- Keep a distance more than 30 cm between the remote control cable and the transmission wire
of Indoor units.
Twist Pair cable: (2 x 0,75mm²)
50
(Terminal Board side)
Standard shielded cable: (2 x 0,75mm²)
2
(Terminal Board side)
Cable Model
PRC-10E1
PRC-15E1
PRC-20E1
PRC-30E1
ELECTRICAL WIRING
Solderless terminal
(X Type 1.25-3X)
100
(Remote Control Switch side)
Solderless terminal
(X Type 1.25-3X)
(Remote Control Switch side)
Length (m)
10
15
20
30
/
3
7