18 | english
5.3
Connection of the power supply
The pump must be protected on-site and must be connected to an external mains switch. All ca-
bles used must have a heat resistance of up to 85 °C. They must not be in contact with the pipe or
the pump and motor casing. All cables must be connected in accordance with EN 60204-1 and EN
50174-2: 2000. The electrical connection must be made as indicated on the nameplate.
ModulA...
ModulA 25-4 180
ModulA 25-6 180
ModulA 25-8 180
ModulA 25-10 180
ModulA 25-12 180
ModulA 32-4 170
ModulA 32-6 170
ModulA 32-8 170
ModulA 32-10 170
ModulA 32-12 170
ModulA 32-4 180
ModulA 32-6 180, ModulA-D 32-6 180
ModulA 32-8 180, ModulA-D 32-8 180
ModulA 32-10 180
ModulA 32-12 180, ModulA-D 32-12 180
ModulA 32F-6 220, ModulA-D 32F-6 220
ModulA 40-4 220
ModulA 40-6 220, ModulA-D 40-6 220
ModulA 40-11 250
ModulA 50-11 220
Example of a typical mains connection, 1x230V ±10%, 50 / 60Hz
L
N
1
Protection
FI
Nominal current [A]
0.08 – 0.37
0.08 – 0.62
0.08 – 0.85
0.08 – 1.15
0.08 – 1.36
0.08 – 0.48
0.08 – 0.73
0.08 – 0.97
0.08 – 1.25
0.08 – 1.36
0.08 – 0.48
0.08 – 0.73
0.08 – 0.97
0.08 – 1.25
0.08 – 1.36
0.08 – 0.73
0.08 – 0.74
0.08 – 1.47
0.08 – 1.39
0.08 – 1.39
2
external switch
961807_01
Output P
[W]
1
7 – 49
7 – 83
7 – 115
7 – 153
7 – 181
7 – 66
7 – 102
7 – 134
7 – 169
7 – 182
7 – 66
7 – 102
7 – 134
7 – 169
7 – 182
7 – 102
11 – 97
11 – 185
8 – 182
8 – 182