Safety
Safety instructions
Make sure that any person installing and operating the CRS
IEEE::
• Is technically qualified and competent
• Fully comply with these assembling instructions
Improper operations or misuse could cause danger to:
• life and limb.
• the equipment and other assets of the operator.
• the equipment proper function.
Safety instructions in this manual are shown in three diffe-
rent forms to emphasize important information.
WARNING
This information indicates particular danger to life and health.
Disregarding such a warning can lead to serious or fatal injury.
CAUTION
This information indicates particular danger to equipment or
other property of the user. Serious or fatal injury cannot be
excluded.
This notes give important or specific information concerning the
equipment or as to work with the equipment.
Safety notes on the equipment operation
Electrical installation is subject to the relevant national
safety rules.
CAUTION
Installation, electrical connection and fitting the device may only
be performed by qualified personnel and only in accordance to
this instruction manual.
It is the responsibility of the user to ensure that the device is
used for specified application only.
For safety reasons, please avoid any unauthorized and improper
usage.
WARNING
All relevant fire regulation must be strictly followed.
4
NOTE
COMBINED RESIN SILICON BUSHINGS, TYPE CRS IEEEE
Product description
These instructions are applicable to CRS IEEE combined
insulation bushings with rated voltages from 25 kV to 34.5
kV and rated currents from 2000 A to 3000 A.
These bushings are designed to operate with the upper
part in air and the lower part immersed in the transformer
oil. CRS IEEE insulation bushings have been designed and
produced in conformity with the following standards:
• IEEE C57.19.100-1995
• IEEE C57.19.01-2000
• IEEE C57.19.00-2004
• IEC 60137, Edition 6
Installation
CAUTION
The operating and installation requirements described in this
manual must be strictly followed. If not, the device can be
damaged or a malfunction may occur.
Assembly on the transformer tank
Make a hole with diameter D (see Table 5B) in the transfor-
mer tank, ensuring there are no uneven surfaces that could
cause problems for correct operation of the bushing.
The stud bolts for securing the bushing (see Table 5B) must
be placed along a circumference of diameter D1-D2 coaxial
with the hole made previously (Figure 1).
Position the gasket provided (Figure 1).
The bushing must be positioned as shown in Figure 2, apply
a tightening torque of 18 lbft (25 Nm) to fix the nuts on the
flange.