INFOSEC UPS SYSTEM E6 LCD RT Evolution 5 KVA Guía De Usuario página 19

Ocultar thumbs Ver también para E6 LCD RT Evolution 5 KVA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5) Calibration
Interface
6) Other settings (available on all operation modes)
Interface
Description
1.
Batt: Calibrate the battery voltage measurement. Calibration
range is from 0V to 5.7V. The default value is 0V. It is available
on all operation modes.
2.
Inv: Adjust the inverter output voltage; the adjustable range is
from 0V to 6.4V, the default value is 0V. It is only available in line
/ battery / converter mode;
3.
Chg: Adjust the Charger output voltage; the adjustable value is
from 0V to 6.9V, the default value is 0V. It is only available in
bypass / line / ECO /converter mode.
(NOTE: Before making charger output voltage adjustment, be
sure to disconnect all batteries first to get the accurate charger
voltage; Be careful that the adjustment should be suitable to
battery specifications, or the battery maybe destroyed.)
Description
Hot standby:
Enable: Hot standby function is enabled. It means that the current
UPS is set to be host of hot standby system, and it will automatically
restart after AC recovery even without battery connected.
Disable: Hot standby function is disabled. The UPS is running at
normal mode and can't restart without battery.
Disable is default setting.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 208 13
19

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

E6 lcd rt evolution 6 kvaE6 lcd rt evolution 8 kvaE6 lcd rt evolution 10 kvaE6 lcd rt evolution 5 kva sE6 lcd rt evolution 6 kva sE6 lcd rt evolution 8 kva s ... Mostrar todo

Tabla de contenido