BATTERY
Battery type
Recharging voltage
Number
Standard model
Typical recharge time
Charging current (max)
Backup time
Typical recharge time
Long backup time model (S)
Charging current (max)
DISPLAY
LCD screen
AUDIBLE ALARMS
Battery mode
Low battery
Overload
Fault
MANAGEMENT / COMMUNICATION
Communication
Parallel connection
ENVIRONMENT
Ideal environment
Operating Altitude
Noise level
Heat dissipation max - LV (110 V)
Heat dissipation max - HV (230 V)
NORMS
Standard
EMC (Electromagnetic compatibility)
Low voltage (Safety)
SALES INFO
Warranty
Gencods - standard versions
Gencods - Long backup time version (S)
* LV (110V) and HV (230V) are different products
** When using internal batteries from 18-19, the unit will de-rate according to below formula : P=Prating x N/20
■Product specifications are subject to change without further notice.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 208 13
E6 LCD RT
E6 LCD RT
EVOLUTION
EVOLUTION
5000 (S)
6000 (S)
12 V / 7 AH
12 V / 7 AH
240 Vdc
20**
20**
7 hours recover to
7 hours recover to
90% capacity
90% capacity
From 4 to 30 minutes depending on the connected load
Depending on the capacity of external batteries
Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator
Sounding every 4 seconds
Sounding every second
Sounding twice every second
Continuously sounding
USB & RS232 port and Infopower included software
(support Windows family, Linux, Unix and MAC)
Optional SNMP
Parallel port
0 - 95% relative humidity @ 0-40° non condensing
Up to 1000 m above sea level (> 1000 m 1% deterioration for every 100 m)
less than 58dBA @ 1 meter
-
-
600 W / 2047,8
600 W / 2047,8
Btu/h
Btu/h
CE RoHS, cTUVus
EN 62040-2 : 2006
EN62040-1 : 2008, UL1778/R:2006;CSA C22.2 NO.107.3-05/R:2006
2 years
3700085 67119 1
3700085 67120 7
3700085 67123 8
3700085 67124 5
E6 LCD RT
E6 LCD RT
EVOLUTION
EVOLUTION
8000 (S)
10000 (S)
12 V / 9 AH
12 V / 9 AH
240 Vdc
20**
20**
9 hours recover to
9 hours recover to
90% capacity
90% capacity
1A
4A
less than 60dBA @ 1 meter
-
-
600 W / 2047,8
600 W / 2047,8
Btu/h
Btu/h
3700085 67121 4
3700085 67122 1
3700085 67125 2
3700085 67126 9
25

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

E6 lcd rt evolution 6 kvaE6 lcd rt evolution 8 kvaE6 lcd rt evolution 10 kvaE6 lcd rt evolution 5 kva sE6 lcd rt evolution 6 kva sE6 lcd rt evolution 8 kva s ... Mostrar todo

Tabla de contenido