Technical Data - Wieland SNE 4012K Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 10
7

Technical data

Control circuits B1 or B2
Rated voltage U
N
Operating voltage range U
Rated power
Nominal current
Max. peak current
Max. line resistance
Response time t
A
Release time t
R
Recovery time t
W
Display
Output circuits
Enabling current paths
Contact type
Contact material
Rated switching voltage
Max. thermal permanent current I
Switching capacity
Utilisation category according to
DIN EN 60947-5-1
Mechanical service life
Conditional short circuit current
Short circuit protection
Max. total current  I
² at 45
n
Max. total current  I
² at 65
n
Signalling current paths
Contact type
Contact material
Rated switching voltage
Max. thermal permanent current I
Terminal and connection data
Connection cross sections
- Single-core or finely stranded
- Finely stranded with wire-end ferrule according to
DIN 46228
AWG conductor size (only use Cu wires)
Maximum tightening torque
Stripping length
Safety
Safe separation
Rated voltage
Surge voltage category
Rated surge voltage
Degree of soiling
Basic isolation
Rated voltage
Surge voltage category
Rated surge voltage
Degree of soiling
General data
Weight
Ambient operating temperature/storage temperature
Air and creepage paths
Approvals, licenses
Standards
8
Assembly, installation and dimensions
on page 19
Doc. # BA000860 – 10/2012 (Rev. B)
B
TH
TH
SNE 4012K / 4024K
SNE 4,012K-A/C
24V DC
0.75 - 1.25 × U
N
0.7 W
30 mA
110 mA
 (5 + (1.333 x U
/ U
- 1) x 200) Ohm
B
N
< 15 ms
< 15 ms
 30 ms
1 LEDs, green
Relay group K1: 13/14, 23/24
Forced, normally open
Ag - alloy, gold plated
230 V AC
6 A
0.1 W .. observe 240W load limit curve; 3 VA to 2,000 VA
AC-15: Ue = 230 V, Ie = 3 A
DC-13: Ue = 24 V, Ie = 1 A
6
10 x 10
518 A (normally open)
Fuse max. 6 A gG / fuse integral < 100 A²s
72 A²
72 A²
* K1 or K2 activated, ** K1 und K2 activated simultaneously
Relay group K1: Y1/Y2
Forced, normally closed
Ag - alloy, gold plated
230 V AC
1 A
Screw terminals (1 terminal point)
1 x 0.2 mm² to 2.5 mm²
2 x 0.2 mm² to 1.0 mm²
1 x 0.25 mm² to 2.5 mm²
2 x 0.25 mm² to 1.0 mm²
26–14
0.5 to 0.6 Nm (5-7 lbf-in)
Control circuit and signalling current path against enabling current paths
300 V
IV
6 kV
2 inside, 3 outside
Control circuit against signalling current path and enabling current path
mutually
300 V
III
4 kV
2 inside, 3 outside
0.145 kg
-25...+65 / -25...+75°C
according to DIN EN 60664-1
TÜV
EN ISO 13849-1, EN 62061, EN81-1, EN 50156-1, UL 508, CSA 22.2
No.14 - M10
SNE 4024K-A/C
1.4 W
2 x 30 mA
2 x 110 mA
2 LEDs, green
Relay group K1: 13/14, 23/24
Relay group K2: 33/34, 43/44
6 A, observe derating
2 x 72 A²
1 x 72 A² *, 2 x 8 A² **
Relay group K1: Y1/Y2
Relay group K2: Y3/Y4
Spring-loaded terminals (2 terminal
points)
1 x 0.2 mm² to 1.5 mm²
1 x 0.25 mm² to 1.5 mm²
(trapezoid crimping)
24–16
7 mm
0.180 kg