Briggs & Stratton P ower P roducts Automatic Transfer Switch
Installation
and Owner's
Manual
Equipment
Description
These switches are a new generation of transfer switches
that are intended to transfer the entire load of normal
residential installations.The
load is connected either to
utility power (normal) or home standby power
(emergency).The
transfer switch monitors
utility and
generator voltages and will automatically
connect to the
appropriate
source of power.
Major components
of the transfer switch are a 2 pole
double throw
transfer switch, control
circuit board, fused
utility terminals
and interconnecting
wiring.
The transfer switch is solenoid-operated
from utility or
generator
inputs and contain suitable mechanical and
electrical
interlock switches to eliminate the possibility of
connecting the utility service to the generator
output. It
has ratings capable of switching full utility power into the
residence. In addition, a manual override
lever is provided
for the transfer function.
The control circuit board has active circuits sensing utility
and generator voltages. It creates a signal for the generator
start-up, switch transfer, retransfer when utility is restored
and generator cool down periods.The
control board also
contains red and green LED's indicating the power sources
available and two relay operated contacts that provide
supervisory control of external loads.
INSTALLATION
Unpacking
Delivery
Inspection
After removing the carton, carefully inspect the transfer
switch components
for any damage that may have occurred
during shipment.
IMPORTANT:
If loss or damage is noted at time of
delivery, have the person(s) making delivery note all damage
on the freight bill and affix his signature under the
consignor's memo of loss or damage. If loss or damage is
noted after delivery, contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Shipment
Contents
• Automatic
Power Transfer Switch
• Installation and Owner's
Manual
Mounting
Dimensions
Figure I depicts the physical size and mounting hole
locations of the NEMA 3R automatic transfer switch
enclosure.This
enclosure is suitable for indoor/outdoor
use.
L
Enclosure
Dimensions
Mounting
Dimensions
Model 01813
16'
Enclosure
Dimensions
<-----_
1,.----------_11.
@
@
@
@
Mounting Dimensions
Model 01814
The transfer switch enclosure is commonly
secured
through the predrilled
holes, as shown.
06"