Installation Instructions - Sure-Lites APC7RG/APCH7RG/APXH7RG/APC7RGSAL Exit and
WALL MOUNT INSTALLATION
1.
De-energize the circuit at the junction box (J-box) where
the exit sign is to be installed.
2.
Remove the exit sign stencil from the EXIT frame.
Remove and discard the plastic canopy from inside the
EXIT.
3.
Drill out the appropriate mounting pattern and the wire
pass hole in the EXIT backplate to fit the J-box being
used.
4.
Feed the red, black, and white wires through the center
hole.
5.
Connect the J-box wires to the EXIT power supply
wires using the wire nuts provided. Connect the white
wire to neutral. If using 120V, connect the black wire to
the hot lead. If using 277V, connect the orange wire to
the hot lead. Cap the unused lead. Press the wires into
the J-box.
6.
Secure the EXIT to the wall and/or junction box using
installer supplied hardware.
7 .
Attach battery leads to PCB.
8.
Determine if a red or green exit is desired. Unit is
shipped ready to display red letters. If green is desired,
shift the jumper on the LED PCB (see Schematic) and
replace the red lens in the stencil with the green lens
(provided).
9.
Snap the EXIT stencil onto the frame.
10. Energize AC supply, LED display will come on. LED
heads will illuminate briefly.
CEILING OR END MOUNT INSTALLATION
1.
De-energize the circuit at the junction box (J-box) where
the exit sign is to be installed.
2.
Remove the exit sign stencil from the EXIT frame.
3.
Remove the canopy kit from inside the EXIT.
4.
Place the provided screws in the canopy screw holes.
Tabs inside the holes will prevent the screws from
falling out during installation.
5.
Remove the appropriate mounting hole plug on the top
(ceiling mount) or side (end mount) of the frame.
6.
Place the canopy nose through the mounting hole
until the side of the frame touches the canopy. Lock
the frame onto the canopy by sliding the frame in
a direction parallel to the canopy length toward the
narrow end of the mounting hole. Slide the frame until
both snaps engage the canopy nose preventing any
motion back out of the hole.
7 .
Feed the red, black, and white wires through the
canopy nose.
8.
Feed the wires from the J-box through the steel
mounting plate and then attach the mounting plate to
the J-box with installer provided hardware.
9.
Connect the J-box wires to the EXIT power supply
wires using the wire nuts provided. Connect the white
wire to neutral. If using 120V, connect the black wire to
the hot lead. If using 277V, connect the orange wire to
the hot lead. Cap the unused lead. Press the wires into
the J-box.
10. Secure the EXIT canopy to the steel mounting plate
using the screws placed in the canopy in step 4.
11. Attach battery leads to PCB.
12. Determine if a red or green exit is desired. Unit is
shipped ready to display red letters. If green is desired,
shift the jumper on the LED
replace the red lens in the stencil with the green lens
(provided).
13. Snap the EXIT stencil onto the frame.
14. Energize AC supply, LED display will come on. LED
heads will illuminate briefly.
COOPER LIGHTING SOLUTIONS
IB50510123
Emergency Light Combo
PCB (see Schematic) and
Installation Instructions