1. General Description and Working
Principle
45PAM100 is a wireless addressable manual call point
designed for operation with Comelit series wireless
expander modules*. In stand-by mode, the resettable
(frangible) call point element is in a
middle position and the status LED is off.
* Refer to the installation manuals of 45TRC100,
45TRA100 and 45TRS100 wireless expander modules for
detailed information about the programming menus and
other details.
To initiate a fire alarm or evacuation event, press on the
resettable element – it moves down and a color strip
is shown on at its upper side. The call point is in "Fire
alarm" condition and the status LED starts blinking fast.
To reset the flexible element back in stand-by mode, use
the special key tool included in the kit - fix the long side
of the tool at the call point's bottom side and push it up
until flexible element moves up in middle position – a
click is heard. Then reset the fire alarm control panel.
Attention. In case of fire alarm event and no connection
between the device and the expander module are applied
the following working algorithms for conservation of the
call point power battery:
- The connection between the device and the
expander module is lost and after that the call point
is activated. In this case the status LED flashes 3 times
and stops.
- The call point is activated, the status LED is
blinking fast and after that the connection between
the device and the expander module is lost. In this
case the status LED will proceed blinking fast for 5
minutes and after that will stop if the connection with the
expander module is not restored during that period.
When the connection between the expander module and
the device is restored and the call point is still activated
(the color strip is visible), the status LED will proceed
blinking fast until resetting the call point.
2. Technical Specifications
Communication range with
expander module
Battery power supply 1 x CR123A 3V
Battery life ~10 years
Radio frequency 868MHz
Communication type Bidirectional
Communication Protocol Wireless Comelit
Radio signal modulation type GFSK
Number of frequency channels 6 pair channels
Radiated power ≤ 20 mW
Receiver category (EN300-220-1) 1.5
Trace attenuation ≥ -90dBm (during the
Test transmission message
period
Type A
Type of the frangible element
Resettable
Operation temperature -10°C to +55°C
Related humidity resistance (93±3)% @ 40°С (no
Enclosure box type ABS
Dimensions 90x57x90mm
Color RAL 3020 (red)
Protection IP40
Weight (with battery) 158g
6
1500m
installation)
300s
(flexible)
condensation)
Mounting Wall, Indoor use
Standards EN 54-11; EN 54-25
3. Installation Place and Mounting
See figure 4 on page 3
4. PCB Elements
The PCB of the manual call point is factory mounted at the
back side of the carrier unit.
1
Enroll
LED
-
CR123A 3V
1. Enroll button. The button is used for the following
actions:
- Enrolling the device to the expander module.
- Checking the signal strength.
- Reset the device.
2. Bi-color operation LED (green/red). The LED is used
for following the actions during enrollment, reset and
checking the signal strength.
3. Tamper switch
4. Power Battery CR123A 3V
Attention: Use only batteries from the same type!
5. Antenna
Attention: Do not touch or bend the antenna!
5. Enrolling to Expander Module
1. Remove the box bottom to access the PCB with the
battery compartment. If the device is not new, perform
reset as described in item 7.
2. Enter in programming mode of the Comelit expander
module. Select ADD DEVICE menu and press ENTER
button. A list with already enrolled devices is shown on
the screen with an order number and type of the device.
3. Scroll down to find a free address to enroll the call
point. Every free address is labeled as EMPTY.
4. Press ENTER button. Message SEARCHING >>>
(arrows are blinking) appears on the screen showing that
the module is scanning for signals from wireless device in
its covering range.
Note: If there is no signal from the device in 2-minute
period, the expander module will exit automatically the
programming mode.
5. Power on the call point - remove the protective
folio from the battery if it is new - and single press the
2
3
4
+
5