Direct
Electrical
Connection
to the Circuit
Breaker,
Fuse Box or Junction
Box
If the appliance is connected directly to the circuit
breaker, fuse box or junction box, use flexible, armored
or nonmetallic
sheathed copper cable (with grounding
wire). Supply a U.L. listed strain-relief
at each end of
the cable. At the appliance end, the cable goes through
the Direct Connection
Hole (see Figure 5) on the
Cord Mounting Plate. Wire sizes (copper
wire only)
and connections
must conform to the rating of the
appliance. A 50A time-delay fuse or circuit breaker is
recommended
(minimum 40A).
Where local codes permit connecting
the
appliance=grounding
conductor
to the neutral
(white) wire (see Figure 5):
1. Be sure that no power is supplied on the cable from
residence.
2. Remove the grounding strap from the terminal block
and from the appliance frame.
3. In the circuit breaker, fuse box or junction box:
a) Connect the green (or bare copper) wire, the
white appliance cable wire, and the neutral (white)
wire together.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
Cable from Residence
Neutral
"'_
(white) Wire _
:::::::-:_:::..
i:,,.
,
Wirde
s_
Red
_(/_
_ _i:i_
--/
(or Bare Copper)
Wire
Cable from
Appliance
--
Black
Wires-
Box
Wire
NOTE: Be sure to remove the
supplied grounding strap.
Figure 5
3=Wire (Grounded
Neutral)
Electrical
System
(Example:
Junction
Box)
U.L.-tisted
Conduit
Connector (or CSA
listed)
Where local codes DO NOT permit connecting
the appliance=grounding
conductor
to the neutral
(white) wire, or if connecting
to 4-wire electrical
system
(see Figure 6):
1.
Be sure that no power is supplied on the cable
from residence.
2.
Remove the grounding strap from the terminal
block and from the appliance frame.
3.
In the circuit breaker, fuse box or junction box:
a) Connect the white appliance
cable wire to the
neutral (white) wire.
b) Connect the 2 black wires together.
c) Connect the 2 red wires together.
d) Connect the green (or bare copper) grounding
wire to the grounding wire of the circuit breaker,
fuse box or junction box.
Cable from Residence
Green (or Bare_r.._.._
_--_
Copper) Wire
White Wire
Red--_
_
/,//_
....
/-
__
Black
Wires
Green (or
Copper) Wire_
_._=
i WihiteWir!
Junction
_.-_1:
U.L-listed Conduit
Box
Connector (or CSA
Cable from
listed)
Appliance
NOTE: Be sure to remove the
supplied grounding strap.
Figure 6 = 4-Wire Electrical
System
(Example:
Junction
Box)
Cabinet
Construction
To eliminate the risk of burns or fire
by reaching over heated surface units, do not have
cabinet storage space above the range. If there is
cabinet storage space above range, reduce risk by
installing a range hood that projects horizontally
a
minimum of 5" (12,7 cm) beyond the bottom of the
cabinet.
Countertop
Preparation
• The cooktop sides of the range fit over the cutout
edge of your countertop.
• If you have a square finish
(flat) countertop,
no
countertop
preparation
is required. Cooktop sides lay
directly on edge of countertop.
• Formed front-edged
countertops
must have
molded edge shaved flat 3/4" (1,9 cm) from each
front corner of opening (Figure 7).