Bri_s & Stratton Power Products Home Generator
Installation Manual
INSTALLATION
PROCEDURES
Unpacking
Precautions
The unit is shipped bolted to its mounting pad, ready for
installation. Avoid damage from dropping, bumping, collision,
etc. Store and unpack carton with the proper side up, as
noted on the shipping carton.
CAUTION
• Observe
that the 15 Amp fuse has been removed
from the
control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring
has
been completed
and inspected.
Delivery
Inspection
After removing the carton, carefully inspect the Home
Standby Generator
for any damage that may have occurred
during shipment.
IMPORTANT:
If loss or damage is noted at time of
delivery, have the person(s) making delivery note all damage
on the freight bill and affix his signature under the
consignor's memo of loss or damage. If loss or damage is
noted after delivery, separate the damaged materials and
contact the carrier for claim procedures. Missing or
damaged parts are not warranted.
Shipment
Contents
The Home
Standby
Generator
is supplied with:
• Home Standby Generator
• Pre-attached mounting pad
• One 24" flexible hook-up hose
• Installation and start-up manual (P/N 192385GS)
• Owner's
manual(P/N
192384GS)
• Illustrated
parts list manual (P/N 193208GS for
model 01815 or P/N 193918GS for model 01938)
• Product warranty sheet (P/N 190881GS)
• Installation checklist (P/N 190840GS)
• Three access door keys
• Four lifting hole plugs
• Oil fill spout
• Touch-up paint
• One spare 15A fuse
• Diagnostic LED kit (diode/plate/decal/pin
connectors
(2))
Required
Specialty
Tools/Equipment
• Two 48" lengths of I" OD pipe (NOT
conduit)
• Hole punches for 16ga steel
• Torque screwdriver, 5 to 50 inch-pound
range
Approved
Transfer
Switches
The Home Standby Generator
should be used ONLY with
the following
UL approved Transfer Switches. Connection
to any other transfer switch not listed below will void your
equipment
warranty.
• 50A Nema I enclosure, BSPP Model 01917
• 50A Nema 3R enclosure, BSPP Model 01918
• 100A Nema 3R enclosure, BSPP Model 01813
• 100A Nema 3R enclosure w/main
line disconnect, BSPP
Model 01928
• 200A Nema 3R enclosure, BSPP Model 01814
• 200A Nema 3R enclosure w/main
line disconnect, BSPP
Model 01929
Home
Standby
Generator
Location
TO THE INSTALLER:
Consult with the owner(s)
and convey any technical considerations
that might
affect their wishes, before applying these general
guidelines.
Generator Clearances
The generator enclosure must be a minimum of 3 ft. (92 cm)
from combustible material.Leaveat least 3 ft. (92 cm) all
around the enclosure for access to the inside of the enclosure.
The unit's exhaust port must be at least 5 ft. (I 52 cm) from
any building opening (window, door, vent etc.), and the
exhaust must not be able to accumulate in any occupied
area (Figure I).
Port
Exhaust port must be
5 ft (I 52 cm) minimum
distance from building
openings