Note: Because the motor speed during the manual limit switch setting procedure is especially high
(nominal value), precise adjustment could prove difficult. For any adjustment of the "Fully Closed" limit switch
position:
1. Activate the system until the previously set "Fully Closed" limit switch is triggered
2. Remove the motor unit from the motor pulley
3. Manually adjust the position of the overlap rod
4. Fix the motor unit to the motor pulley again
If the installation requires the Power 571/2 to be supplied with power from:
a control box
a radio receiver
a Home and Building Automation unit
the calibration procedure should not be carried out using these pieces of equipment because they
have self-retention commands instead of impulse types (this could cause irreparable damage to the
system).
Removing the motor from the motor pulley is a procedure that demands great care.
Keep all unauthorized persons out of the work zone during this procedure.
Following the instructions in attachment "N" support the motor before pushing the release buttons to
prevent the motor from falling due to its weight.
FAULT
The system does not move
The system does not stop
at the correct position
System blocks after
several consecutive
activations
Technical Characteristics
Electrical supply: 90 - 250 Vac, 50 - 60 Hz (Power 571/1)
Input: 55 W (Power 571/1)
Sliding velocity: 25 cm/s
Radio frequency chip reception frequency: 868 MHz - 915 MHz (Power 571/1)
Single control with SINGLE button (Power 571/1)
Simultaneous control with GROUP button (Power 571/1)
Manufactured to EU standards
Dimensions: 50 mm x 100 mm x 290 mm
Weight: 1,2 Kg (Power 571/1)
Removing the motor
Troubleshooting
POSSIBLE CAUSE
Limit stops incorrectly set
Incorrect wiring
No electrical power
Faulty motor unit.
R. F. association not
carried out (Power 571/1)
Limit stops incorrectly set
Obstructions in the curtain
work space
The power supply has
reached the heat protection
threshold
(see attachments "F" fig. "1F" - "M" fig. "1M" )
130 W (Power 571/2)
2,2 Kg (Power 571/2)
6
Z258 rD
REMEDY
Set the limit stops
Check and correct the wiring by following
the instructions in this manual
Restore electrical power
Request replacement of the motor unit.
Carry out the association procedure
(Power 571/1)
Set the limit stops
Remove obstructions
Let the power supply cool for a few
minutes and try again.
230 Vac, 50 Hz (Power 571/2)