To adjust the CS-50, use controls located under the front cover (lens and ON/OFF button). The wall switch wallplate must be removed to
gain access to the adjustment dial under the ON/OFF button.
1. Remove the wallplate.
2. Firmly grasp the edges of the front cover directly below the lens where it says "open" (see Fig. 5). Push in one side first until it
pops out, then the other side. Remove front cover from the unit.
Adjusting the Time Delay
The factory setting for the time delay dial is fully clockwise, providing the maximum delay of 30 minutes. To reduce the amount of time
the load remains ON after the last motion detection, turn the dial counterclockwise (minimum = 30 seconds). You can set the following
times: 30 minutes, 20 minutes, 10 minutes, 5 minutes, 30 seconds.
Status LED
Push and hold the ON/Off push button twelve seconds to enable and disable the the Status LED indicator light on the ON/OFF button.
The factory default setting is enabled. When enabled the Status LED blinks when the sensor detects motion, whether the load is ON or
OFF.
SENSOR ADJUSTMENT & PROGRAMMING
Fig 5: Remove Front Cover
Time
Delay
Dial
Fig 6: Time Delay Adjustment
CAUTION
Do not overturn the time delay adjustment dial.
T im
e
D e la
3 0 m
y
in .
2 0 m
3 0 se
in .
c.
5 m
1 0 m
in .
in .