Ingeteam
9. AC connection
This chapter explains the requirements and process for connecting the AC wiring to the unit.
Read carefully before starting the connection process.
INFO
Consult section
"Important safety instructions"
For further information about the connection of the inverter within the installation, please see section
Electrical diagram of the
9.1. Safety instructions for the AC connection
DANGER
Make sure there is no voltage present in the unit and that the DC connection has not been made before starting
the AC connection.
Do not switch on the powerto the unit until you have successfully made the rest of the connections.
Use the Personal Protective Equipment specified in the section
Respect the polarity of the AC wiring.
CAUTION
Ingeteam accepts no liability for any damages caused by an incorrect connection.
The communications for this inverter are also powered from the AC section.
9.2. Wiring requirements for the AC connection
A
34
and the following instructions before working on the unit.
system".
D
C
10 ~ 14 mm
B
L
Line
"Personal Protective Equipment
A
B
Diameter
Section
4 mm
for IS
2
3TL
6 mm
for IS
2
6TL M2
1.8 ~ 2.5 Nm
PE
N
PE
Neutral
Ground
ACL2011IQM01_ - Installation and Operation Manual
AC connection
"2.7.
(PPE)".
C
D
Length
Length
8 ~ 9 mm
36 ~ 40 mm
N
L