Descargar Imprimir esta página

Mitsubishi Electric PUZ-HA.NHA2 Serie Manual De Instalación página 8

Ocultar thumbs Ver también para PUZ-HA.NHA2 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Electrical
work
6.2. Field electrical wiring
Outdoor unit model
Outdoor unit power supply
Breaker size
Minimum
circuit ampacity
Maximum
rating of overcurrent
protective
device
Outdoor unit power supply
x
Outdoor unit power supply earth
7d N_ Indoor unit-Outdoor
unit
_ _
Indoor unit earth
Remote controller-Indoor
unit
Outdoor unit L1-L2
_
._
Indoor
unit-Outdoor
unit S1-S2
L_ _
Indoor unit-Outdoor
unit $2-$3
Remote controller-Indoor
unit
HA30, HA36
Single, 208/230 V, 60 Hz
*4
30 A
28 A
40 A
2 x Min. AWG 10
I × Min. AWG 10
"I
3 x AWG 16 (polar)
"I
I × Min. AWG 16
*2
2 x AWG 22 (Non-polar)
*3
AC 208/230 V
*3
AC 208/230 V
*3
DC 24 V
*3
DC 12 V
"I. Max. 45 m, 147ft
If2.5
mm 2 used, Max. 50 m, 164ft
If 2.5 mm 2 used and S3 separated,
Max. 80 m, 262ft
*2. The 10 m, 30 ft wire is attached
in the remote
controller
accessory.
Max 1500 ft
*3. The figures are NOT always against the ground.
S3 terminal
has DC 24 V against S2 terminal.
However
between
$3 and $1, these terminals
are NOT electrically
insulataed
by the transformer
or other device.
*4. Use earth leakage
breaker (NV)
Notes:
1. Wiring size must comply
with the applicable
local and national code.
2. Use copper
supply
wires.
3. Use wires rated 600V or more for the power supply
cables
and the indoor/outdoor
unit connecting
cables.
4. Install
an earth
longer than
other cables.
208/230V
Single phase
Isolator
Sl
A-Control
$2
Outdoor Unit
S3
3 poles
isolator
Y
i
i
i
i
i
__
Sl
$2
A-Control
Indoor Unit
S3
Z_ Warning:
In case of A-control
wiring,
there
is high voltage
potential
on the S3 terminal
caused
by electrical
circuit
design
that has no electrical
insulation
between
power
line and communication
signal
line. Therefore,
please turn off the main power supply
when
servicing.
And do not touch
the Sl, S2, S3 terminals
when the power
is energized.
If isolator
should
be used between
indoor
unit and outdoor
unit, please use 3-pole type.
/_
Warning:
• Turn on the main power when the ambient
temperature
is -20°C, -4°F or higher.
• In below
-20°C, -4°F condition,
it needs at least 4hr standby
to operate
in order to warm
the electrical
parts.
8

Publicidad

loading

Este manual también es adecuado para:

Puz-ha30nha2Puz-ha36nha2