• The appliance shall be stored in a room
without continuously operating ignition
sources (for example: open flames, an
operating gas appliance) and ignition
sources or (for example: an operating
electric heater) close to the appliance.
• The appliance shall be stored so as to
prevent
mechanical
occurring.
• A warning that the appliance shall be
stored in a well-ventilated area where the
room size corresponds to the room area as
specified for operation.
• Any person who is involved with working
on or breaking into a refrigerant circuit
should hold a current valid certificate from
an
industry-accredited
authority,
which
competence to handle refrigerants safely
in accordance with an industry recognized
assessment specification.
• Servicing shall only be performed as
recommended
manufacturer.
Maintenance
requiring the assistance of other skilled
personnel shall be carried out under the
supervision of the person competent in the
use of flammable refrigerants.
• DO NOT modify the length of the power
cord or use an extension cord to power the
unit.
• DO NOT share a single outlet with other
electrical
appliances.
supply can cause fire or electrical shock.
• Please follow the instruction carefully to
handle,
install,
conditioner to avoid any damage or
hazard. Flammable Refrigerant R32 is used
within air conditioner. When maintaining or
disposing
the
refrigerant
(R32
recovered properly, shall not discharge to
air directly.
IMPORTANT SAFETY INSTRUCTIONS
damage
assessment
authorizes
by
the
equipment
and
Improper
power
clear,
service
the
air
conditioner,
or
R290)
shall
• No any open fire or device like switch
which may generate spark/arcing shall be
around air conditioner to avoid causing
ignition of the flammable refrigerant used.
Please follow the instruction carefully to
store or maintain the air conditioner to
prevent
occurring.
from
• Flammable refrigerant - R32 is used in air
conditioner. Please follow the instruction
carefully to avoid any hazard.
• The
refrigerating
receive maintenance, service, or repair by
any person.
• Ensure that the area is in the open or that it
is adequately ventilated before breaking
into the system or conducting any hot
their
work.
continue during the period that the work is
carried out. The ventilation should safely
disperse any released refrigerant and
preferably expel it externally into the
atmosphere.
repair
• Check that cabling will not be subject to
wear,
vibration,
adverse environmental e ects. The check
shall also take into account the e ects of
aging or continual vibration from sources
such as compressors or fans.
• Under no circumstances shall potential
sources of ignition be used in the searching
for or detection of refrigerant leaks. A
halide torch (or any other detector using a
naked flame) shall not be used. The
following leak detection methods are
air
deemed acceptable for all refrigerant
systems. Electronic leak detectors may be
used to detect refrigerant leaks but, in the
case of FLAMMABLE REFRIGERANTS, the
the
sensitivity may not be adequate, or may
be
need re-calibration. (Detection equipment
shall be calibrated in a refrigerant-free
area.) Ensure that the detector is not a
potential source of ignition and is suitable
for the refrigerant used. Leak detection
equipment shall be set at a percentage of
mechanical
damage
system
A
degree
of
ventilation
corrosion,
excessive
sharp
edges
5
from
should
not
shall
pressure,
or
any
other