Descargar Imprimir esta página

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

U
SE
FUNCTION
Time interval for the
Battery test
automatic battery test
Alarm threshold
Selects the overload
for maximum
load
Display
Selects the level of
brightness
brightness of the LCD
Selects the mode of
operation of the sound
Sound alarm
Selects the permitted
range for the input
Input frequency
tolerance
switchover to bypass
synchronization
Selects the permitted
Bypass voltage
voltage range for
thresholds
switchover to bypass
Bypass voltage
Selects the permitted
voltage range for ECO
thresholds for
ECO
mode operation
Selects the sensitivity
Sensitivity of
of intervention during
intervention for
operation in ECO
ECO mode
Power supply of the
Load power
load on bypass with
supply in stand-
UPS switched of
by
(stand-by status)
Selects the mode for
Bypass operation
use of the bypass line
56
DESCRIPTION
PREDEFINED
40 hours
Disabled
user limit
Maximum
Reduced
alarm

ADVANCED FUNCTIONS

frequency for
± 5%
and for output
Low:
High: 264V
Low:
High: 253V
Normal
mode
Disabled
(load NOT
powered)
Normal
POSSIBLE CONFIGURATIONS
• Disabled
• 1 ÷ 1000 in steps of 1 hour
• Disabled
• 0 ÷ 103 in steps of 1%
Minimum ÷ Maximum in 20 steps
• Normal
• Reduced: does not sound for
momentary intervention of the bypass
• ± 0.25%
• ± 0.5%
• ± 0.75%
• ± 1 ÷ ±10 in steps of 1%
180V
Low :
180 ÷ 200 in steps of 1V
High:
250 ÷ 264 in steps of 1V
200V
Low: 180 ÷ 220 in steps of 1V
High:
240 ÷ 264 in steps of 1V
• Low
• Normal
• High
• Disabled (not powered)
• Enabled (powered)
• Normal
• Disabled with input/output
synchronization
• Disabled without input/output
synchronization
MODE