5 -
T
ECHNICAL DATA TABLE
MODELS
INPUT
Nominal voltage
Accepted range
Voltage range ruling out battery intervention
Nominal frequency
(1)
Maximum current
(2)
Nominal current
Power factor
Current distortion @ maximum load
BYPASS
Accepted voltage range for switching
Accepted frequency range for switching
Switching time
BATTERY
Back-up time
No. batteries / V / Ah
Recharge time
OUTPUT
(8)
Nominal voltage
(4)
Static variation
(5)
Dynamic variation
Waveform
Voltage distortion @ linear load
Voltage distortion @ distorting load
(6)
Frequency
Current crest factor
(3)
Nominal power
Nominal power
MISCELLANEOUS
Leakage current to earth
AC/AC efficiency
(7)
Ambient temperature
Humidity
Protections
Safety compliance
EMC compliance
Hold-up time
Noise level
Dimensions H x L x D
Weight
64
[Vac]
[Vac]
[Vac]
Maximum: 276
[Vac]
Minimum: 164 ÷ 84
[Vac]
Return to mains-powered operation: 180
[Hz]
[A]
[A]
[Vac]
[msec]
[min / W]
[h]
[Vac]
(3)
[VA]
[W]
[mA]
[°C]
Excessive battery discharge – Overcurrent – short-circuit
EN 50091-1-1 and directive 73 / 23 / EEC, 93/68 EEC
EN 50091 - 2 cl. B and directive 89/336 EEC, 92/31
[msec]
[mm]
[Kg]
DLD 330
220 / 230 / 240
0 ÷ 276
(from 100% to 50% of load in
linear mode)
50 - 60 +5
15
11
≥ 0.98
≤ 7%
180 ÷ 264
Frequency selected ±5 %
Typical: 2 - Maximum: 4
6' / 2300
9 / 12 / 7 high rate discharge
4 ÷ 8
220 / 230 / 240 ±1.5%
1.5%
≤ 5% in 20 msec
Sinusoidal
≤ 3%
≤ 6%
50 or 60 Hz selectable
≥ 3 : 1
3300
2300
≤ 1
90%
0 – 40
< 90% non-condensing
– Overvoltage – undervoltage - thermal
EEC, 93/68 EEC
≥ 40
< 40 dB(A) at 1 mt.
455 x 175 x 520
38
DLD400
16
12
5'30 / 2400
4000
2400
38