Descargar Imprimir esta página

Riello Dialog Dual Serie Manual De Usuario página 63

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Commands in progress: Indicates presence of a remote command in progress.
CODE
C01
C02
C03
C04
LOCK
The LOCK (block) type report signals are usually preceded by an alarm signal and, on account of their
importance, result in the inverter being switched off and the load being powered through the bypass line (the
procedure is excluded in case of lockouts due to strong and persistent overloads and lockouts following a
short-circuit).
CODE
L03
L04
L05
L07
L10
L13
L20
L21
L40
L41
L42
L43
L50
L51
L52
L53
* In ECO mode, the load is normally powered by the bypass. Therefore, in the presence of a load of constant power,
the current absorbed depends on the mains voltage, which may accordingly be in excess of the value allowed by the
input plug and the protection upstream.
When this situation arises, the UPS reports a failure which automatically disappears if the input voltage increases
and/or the output load is reduced.
DESCRIPTION
Remote shutdown command
Remote load on bypass command
Remote switch-on command
Battery test in progress
DESCRIPTION
Auxiliary power supply incorrect
High temperature on heat sinks
Temperature Sensor1 broken
Temperature Sensor2 broken
Input fuse broken or input relay stuck (does not close)
Capacitor precharging failure
Capacitor bank undervoltage
Capacitor bank overvoltage
Inverter overvoltage
D-C voltage on output
Inverter voltage not right
Inverter undervoltage
Overload: load > 103%
Overload: load > 110%
Overload: load > 150%
Short-circuit
P
ROBLEM SOLVING
63

Hide quick links:

Publicidad

loading

Este manual también es adecuado para:

Dialog dual dld 330Dialog dual dld 400