1. Safety information
- Before installing or using battery, it is important and necessary to read the user manual
carefully. Failure to do so or to follow any instructions or warnings in this document may
result in electric shock, serious injury or death, or may damage the battery, potentially
rendering it inoperable.
- If the battery is stored for long time, it is required to charge them every six months, and
the SOC should be no less than 90%.
- The battery needs to be charged within 12 hours, after full discharge.
- Do not install the product in an outdoor environment, or an environment beyond the
operating temperature or humidity range listed in the manual.
- Do not expose the cable to the outside.
- Do not connect power terminal reversely.
- All battery terminals must be disconnected for maintenance.
- Please contact the supplier within 24 hours if there is something abnormal.
- Do not use detergent to clean the battery.
- Do not expose batteries to flammable or harsh chemicals or vapors.
- Do not paint any part of battery, including any terminal or external components.
- Do not connect battery with PV solar wiring directly.
- The warranty claims are excluded for direct or indirect damage due to items above.
- Any foreign object is prohibited to insert into any part of battery.
1.1 Before connecting
- After unpacking, please check the product and packing list first, if the product is
damaged or missing parts, please contact your local dealer.
- Be sure to cut off the mains power and make sure the battery is in turned off mode.
- Wiring must be correct, do not mistake the positive and negative cables, and ensure no
short circuit with the external device.
- It is forbidden to directly connect the battery and AC power.
- The battery embedded BMS is designed for single battery voltage, please do not
connect the battery in series.
- The battery must be grounded and the resistance must be less than 0.1Ω.
- Please, ensure that the electrical parameters of the battery system are compatible with
related equipment.
- Keep the battery away from water and fire.
1.2 In running
- If you need to move or repair the battery system, you must cut off the power supply and
turn off the battery completely.
- It is forbidden to connect the battery with different types of batteries.
- It is forbidden to connect the battery with a faulty or incompatible inverter.
- It is forbidden to disassemble the battery (the QC label falls off or is damaged).
- In the event of a fire, only dry powder fire extinguishers can be used, and liquid fire
extinguishers are prohibited.
- Please do not open, repair or disassemble the battery except staffs from your seller or
authorized by your dealer. We do not undertake any consequences or related
responsibility which because of violation of safety operation or violation of design,
production and equipment safety standards.