4.3 Grounding
The ground wires must be cables green-
yellow
of
10
AWG
connection, the resistance from the point of
ground connection of the battery to the
connection to the ground rod must be less
than 0.1 Ω.1.
Install a ground cable in communication
with all modules. Use a separate rod. To
connect the ground line to the batteries just
drill a hole in the frame of each battery and
connect with a screw.
NOTE: be sure to drill in a safe place (as
showed in photo to cannot internally
damage the battery.
Sand around the hole well to ensure that
the
paint
does
conductivity.
Do not connect the inverter to this ground
line. The inverter already has its own
ground connection to through AC power.
or
more.
After
not
limit
a
correct