BTL5-S1_ _B-M_ _ _ _-P-(SA244)-S32/S147/KA_ _
Micropulse Linear Transducer in Profile Housing
4

Wiring

Note the following when mak-
ing electrical connections:
System and control cabi-
net must be at the same
ground potential.
To ensure the electromagnetic
compatibility (EMC) which Balluff
warrants with the CE Mark, the
following instructions must be
strictly followed.
BTL transducer and the processor/
control must be connected using
shielded cable.
Shielding: Copper filament
braided, 85 % coverage.
4.1

Connector S32

BKS Connector,
View of solder end
of connector body
BKS-S32M-00
or BKS-S33M-00
Fig. 4-1: Pin arrangement BKS on BTL
Pin
BTL5-S1_ _...S32
Interface signals
1
+Clk
2
+Data
3
–Clk
4
do not connect
5
–Data
Supply voltage (external)
6
GND
7
+24 V
8
do not connect
Table 4-1: Wiring
4.3

Cable KA_ _

+Clk
–Clk
+Data
–Data
GND
+24 V
BTL5-S1_ _
Fig. 4-3: BTL5-S1_ _-...KA_ _ with Processor/Controller, Connection example
6
english
The shield must be tied to the con-
nector housing in the BKS connec-
tor; see instructions accompanying
the connector.
In the cable version the cable
shield is connected to the housing
in the PG fitting.
The cable shield must be grounded
on the control side, i.e., connected
to the protection ground.
Pin assignments can be found in
➥ ➥ ➥ ➥ ➥ Table 4-1, 4-2 or 4-3. Connec-
tions on the controller side may vary
according to the controller and con-
figuration used.
4.2

Connector S147

BKS Connector,
View of solder end
of connector body
BKS-S147M-00 or
BKS-S148M-00
Fig. 4-2: Pin arrangement BKS on BTL
Pin
BTL5-S1_ _...S147
Interface signals
1
–Data
2
+Data
3
+Clk
4
–Clk
Supply voltage (external)
5
+24 V
6
GND
7
do not connect
Table 4-2: Wiring
YE
PK
GY
GN
BU
BN
Processor/
Controller
When routing the cable between
the transducer, controller and
power supply, avoid proximity to
high voltage lines to prevent noise
coupling.
Especially critical is inductive
noise caused by AC harmonics
(e.g. from phase-control devices),
against which the cable shield
provides only limited protection.
Position information is sent over the
RS 485/422 interface as synchro-
nous serial data (SSI) to the host
controller. High noise immunity is
assured by the differential drivers
used for sending and receiving sig-
nals.
Cable length max. 400 m;
Ø 6 to 8 mm.
Caution! False data will result
from reversing the +Clk and –Clk
inputs.
Colors
BTL5-S1_ _...-KA_ _
Interface signals
YE yellow
+Clk
PK ping
–Clk
GY gray
+Data
GN green
–Data
Supply voltage (external)
BU blue
GND
BN brown
+24 V
WH white
do not connect
Table 4-3: Wiring