8.7 Priority of Settings
With Grundfos GO Remote, you can set the motor
to operate at maximum speed or to stop.
If two or more functions are enabled at the same
time, the motor operates according to the function
with the highest priority.
Start/
Grundfos GO Remote or operat-
Priority
stop but-
ing panel on motor
ton
1
Stop
2
Stop
3
Manual
Maximum speed / User defined
4
speed
5
6
7
8
9
10
11
12
Minimum speed
13
14
15
Start
*
Stop and Maximum speed settings made with Grundfos GO Remote or on the motor operating panel can be overruled
by another operating-mode command sent from a bus, for example Start. If the bus communication is interrupted, the
motor resumes its previous operating mode, for example Stop, that was selected with Grundfos GO Remote or the
motor operating panel.
22
If you have set the motor to maximum speed via
the digital input, the motor operating panel or
Grundfos GO Remote can only set the motor to
Manual or Stop.
The priority of the settings appears from the table
below:
Digital input
Stop
User defined speed
Maximum speed
Minimum speed
Start
Bus communication
Stop
Maximum speed / User
defined speed
Minimum speed
Start