Descargar Imprimir esta página

Satco NUVO 65/884 Instrucciones De Instalación Y Seguridad

Paquete led de pared con cct y vataje seleccionable

Publicidad

Enlaces rápidos

CCT & WATTAGE SELECTABLE
LED WALL PACK
Models: 65/884, 65/885
INSTALLATION AND SAFETY INSTRUCTIONS
IMPORTANT: Read before installing fixture. Retain for future reference.
WARNING: Risk of Fire or Electric Shock
• To reduce the risk of fire, electrical shock or injury to persons; read and follow all warnings
and installation instructions before installing.
• All installation should be performed by a qualified electrician.
• To avoid electric shock, ensure power is turned off before installation or inspection.
All wiring must be installed in accordance with Electrical Code and local electrical code.
• To prevent fire, this fixture is rated for use with minimum 90°C rated supply wire.
• This product must be properly grounded.
• To avoid damage and/or product malfunction, do not modify the fixture or replace
accessories without confirming with the supplier first.
• Do not expose wiring to edges of sheet metal or other sharp objects.
• Suitable for outdoor/wet locations. Distance from ground should be more than 2m.
SPECIFICATIONS
Model
Watts
65/884
30W/45W/60W
65/885
70W/85W/100W
INSTALLATION: Wall Mount
STEP 1: Turn power OFF.
Remove (2) M4*20 inner hexagon screws and
open the fixture (see Figure A).
STEP 2: Separate the cover from the base of
the fixture.
STEP 3: Prepare base for mounting by drilling
or knocking out the appropriate hole.
STEP 4: Adhere gasket (see Figure B), align it
with the mounting position. Pass the input wire
through the gasket and the hole on the base,
and secure on the wall or junction box with
screws (not included).
STEP 5: Connect wires according to the
wiring diagram (see Figure C).
STEP 6: Put the cover back on the hinge of
the base of the fixture.
STEP 7: Check the hinge is properly
connected and close the fixture (see Figure D).
STEP 8: Secure fixture with
(2) M4*20 inner hexagon screws. Installation is
complete (see Figure E). Turn power ON.
Wattage & CCT Selectable Instructions
NOTE: Turn OFF the power before adjusting.
• Remove 1/2" NPT plug, adjust wattage and CCT switch according to your requirement.
Default Settings: Watts: 60W & 100W / CCT: 5000K.
• After adjustments are complete, replace the 1/2" NPT plug.
Photocell Function
NOTE: Turn OFF the power before adjusting.
• Unscrew 1/2" NPT transparent photocell plug. Switch ON/OFF according to your requirement.
• After adjustment is complete, replace the 1/2" NPT transparent photocell plug.
© Copyright 2023 Satco Products, Inc. 8/23 v1.2
CCT
3000K/4000K/5000K
A
C
D
(Default Setting: OFF)
Volts
CRI
Operating Temperature
120V-277V
80
-40°C to +50°C (-40°F to +122°F)
(2) M4*20 inner hexagon screws
(L) Fire Line
Black
(N) Neutral Line
White
(G) Ground Line
Green/Yellow Green
Dim +
Purple
Pink
Dim –
Vaux + (12V+)
Black/White
Vaux – (12V–)
Black/White
15 1/2" W x 9 3/4" H x 4 1/4" D
(395mm W x 248mm H x 107mm D)
Adhere
B
Gasket
LED
Driver
0-10V
Dimming
E
Satco Products, Inc.
Brentwood, NY 11717

Publicidad

loading

Resumen de contenidos para Satco NUVO 65/884

  • Página 1 NOTE: Turn OFF the power before adjusting. • Unscrew 1/2" NPT transparent photocell plug. Switch ON/OFF according to your requirement. • After adjustment is complete, replace the 1/2" NPT transparent photocell plug. Satco Products, Inc. © Copyright 2023 Satco Products, Inc. 8/23 v1.2 Brentwood, NY 11717...
  • Página 2 PAQUETE LED DE PARED CON CCT ESPAÑOL: Y VATAJE SELECCIONABLE INSTRUCCIONES DE INSTALACIÓN Y SEGURIDAD Modelos: 65/884, 65/885 IMPORTANTE: Lea esto antes de instalar el accesorio. Consérvelo para referencia futura. SEGURIDAD: Riesgo de incendio y descarga eléctrica • Para disminuir el riesgo de incendio, choque eléctrico o lesiones, lea todas las advertencias y siga todas las instrucciones antes de instalarla.

Este manual también es adecuado para:

Nuvo 65/885