Specifications
Model
Nominal voltage and input range
Nominal input frequency and tolerance
Nominal output voltage
Nominal output frequency
Output voltage regulation in
line-mode
Output voltage regulation in
battery mode
Nominal output power in W / VA
Output voltage waveform
Maximum output current @ P . F.
Efficiency with nominal load
Maximum operating altitude
at 100% of nominal power
Online overload capability
Overload capacity in battery mode
Current limitation
Autonomy time at full load
Battery recharge time
Transfer time
Outlets
Maximum input current
SMART750RMXL2U
120V~, 83-147V
60 Hz (+/- 5 Hz)
120V~ in line mode
and 120V~ in battery
mode
60Hz (+/- 0.5 Hz)
120 V~ (+8% / - 21%)
120 V~ (+/-5%)
600W / 750VA
Sinusoidal in line mode
and in battery mode
6.3A
P .F. = 0.8
95%
6561 ft. (2000 m)
125% for 10 minutes
105% @ 0.5 seconds
10A
8.3 minutes @ 600W
4.5 hours
2 milliseconds typical
(4 milliseconds max)
6x 5-15R outlets with
battery backup,
regulation and surge
7.5A
20
SMART1000RM2U
120V~, 83-147V
60 Hz (+/- 5 Hz)
120V~ in line mode
and 120V~ in battery
mode
60Hz (+/- 0.5 Hz)
120 V~ (+8% / - 21%)
120 V~ (+/-5%)
800W / 1000VA
Sinusoidal in line mode
and in battery mode
8.3A
P .F. = 0.8
95%
6561 ft. (2000 m)
125% for 10 minutes
105% @ 0.5 seconds
10A
5.3 minutes @ 800W
4.5 hours
2 milliseconds typical
(4 milliseconds max)
2 milliseconds typical
(4 milliseconds max)
9.2A