OPERATING AND MAINTENANCE MANUAL
DIGI-PLUS SERIES CONTROLLER
12. PRESSURE SENSOR CALIBRATION
In case of wrong lecture of the pressure sensor it can be adjusted again. For the pressure
sensor calibration is necessary to have a pressure gauge in the installation. Proceed
following next steps:
ZERO REGULATION
1. Open the taps living the hydraulic net without pressure.
2. Press simultaneously the buttons
3. Press
to validate.
FULL SCALE
1. Start the pump until cut-out of the pressure switch.
2. Press simultaneously the buttons
3. Adjust the pressure with the arrows push-buttons to get the pressure desired.
4. Press
to validate.
Remark: pressure sensor decalibration should not be a normal event. If it is frequently
repeated contact the technical service.
13. WARNINGS AND ALARMS
COD.
ALARM
www.proindecsa.com / proindecsa@proindecsa.com
and
and
DESCRIPTION
until the display show 0.0 flashing.
till the display flashes with a figure.
SYSTEM REACTION